Wind Damage >> Protecting Against Hurricanes

Attachment of Brick Veneer in High-Wind Regions Table 1. Brick Veneer Tie Spacing Wind Speed (mph)(3-Second Peak Gust) Maximum Vertical Spacing for Ties 16" stud spacing 24" stud Protecting Against Hurricanes spacing 90 18.0a 16.0a 100 18.0a 16.0a 110 18.0a 14.8 120 18.0a NAb 130 15.9 NAb 140 13.7 NAb 150 10.2 Nab 

Wind Pressure (psf) Maximum Vertical Spacing for Ties 16" stud spacing Protecting Against Hurricanes 24" stud spacing 17.8 18.0a 16.0 a 22.0 18.0a 16.0 a 26.6 18.0a 14.8 31.6 18.0a NA b 37.1 15.9 NA b 43.0 13.7 NA b 49.4 10.2 Na b Notes: 1. 

The tie spacing is based on wind loads derived from Method 1 of ASCE 7-02, for the corner area of buildings up to 30' high, located in Exposure B with an importance factor (I) of 1.0 and no topographic influence. For other heights, exposure, or Protecting Against Hurricanes importance factor, an engineered design is recommended. 2. 

Fastener strength is for wall framing with a Specific Gravity G=0.55 with moisture contents less than 19% and the following adjustment factors, Protecting Against Hurricanes Ct=0.8; and CD, CM, Ceg, and Ctn=1.0. 3. 

Nail embedment depth of 2" for 2.5" long 8d common (0.131" diameter) ring- shank fasteners a Maximum spacing allowed by ACI 530-05 b 24" stud spacing exceeds the maximum horizontal tie spacing of ACI 530-05 prescribed for wind speeds over 100 mph [End table] Attachment of Protecting Against Hurricanes Rooftop Equipment in High-Wind Regions

Hurricane Katrina Recovery AdvisoryMay 2006, Revised July 2006FEMA Purpose: To recommend practices for designing and Protecting Against Hurricanes installing rooftop equipment that will enhance wind resistance in high-wind regions. [Begin text box]

Note: For attachment of lightning protection systems, see Hurricane Katrina Recovery Advisory on Protecting Against Hurricanes Rooftop Attachment of Lightning Protection Systems in High-Wind Regions. [End text box] Key Issues Rooftop equipment frequently becomes detached from rooftops during hurricanes. 

Water can enter the building at displaced equipment (see Figure 1); displaced equipment can puncture and Protecting Against Hurricanes tear roof coverings (thus allowing water to leak into the building). Equipment blown from a roof can damage buildings and injure people. Damaged equipment may no longer provide service to the building. Figure 1 caption. 

This gooseneck was attached with only two small screws. A substantial amount of water was able to enter the building during the hurricane. [end of caption] Construction Guidance Mechanical Penthouse: Protecting Against Hurricanes By placing equipment in mechanical penthouses rather than being exposed on the roof, equipment within penthouses is shielded from high-wind loads and windborne debris. 

Therefore, use of mechanical penthouses designed and constructed in accordance with a current building code are recommended, Protecting Against Hurricanes particularly for critical and essential facilities.Design Loads and Safety Factors: Loads on rooftop equipment should be determined in accordance with the 2005 edition of ASCE 7. Figure 2 caption. 

This 30’ x 10’ x 8’ 18,000-pound HVAC unit was attached to its curb with 16 straps (one screw per strap). Although the wind speeds were Protecting Against Hurricanes estimated to be only 85 to 95 miles per hour (3-second peak gust), it blew off the building. [end of caption] 

Note: For guidance on load calculations, see "Calculating Wind Loads and Anchorage Requirements for Rooftop Equipment,” ASHRAE Journal, volume 48, number 3, March 2006. A minimum safety factor of 3 is recommended for critical and essential facilities, and Protecting Against Hurricanes a minimum safety factor of 2 is recommended for other buildings. 

Loads and resistance should also be calculated for heavy pieces of equipment (see Figure 2). Simplified Attachment Table: To anchor fans, small HVAC units, and relief air hoods, Protecting Against Hurricanes the following minimum attachment schedule is recommended (see Table 1) (note: the attachment of the curb to the roof deck also needs to be designed to resist the design loads):   

Number of #12 Screws for Base Case Attachment of Rooftop Equipment Case No.: 1 Curb Size and Equipment Type: 12”x 12” Curb with Protecting Against Hurricanes Gooseneck Relief Air Hood Equipment Attachment: Hood Screwed to Curb Fastener Factor for Each Side of Curb or Flange: 1.6 Case No.: 2Curb Size and Equipment Type: 12”x 12” 

Gooseneck Relief Air Hood with Flange Equipment Attachment: Flange Screwed to 22 Gauge Steel Roof Deck Fastener Factor for Each Side of Curb or Protecting Against Hurricanes Flange: 2.8 Case No.: 3Curb Size and Equipment Type: 12”x 12” Gooseneck Relief Air Hood with FlangeEquipment Attachment: Flange Screwed to 15/32” OSB Roof Deck 

Fastener Factor for Each Side of Curb or Flange: 2.9 Case No.: 4Curb Size and Equipment Type: 24”x 24” Curb with Gooseneck Relief Air HoodEquipment Attachment: Hood Screwed to Protecting Against Hurricanes Curb Fastener Factor for Each Side of Curb or Flange: 4.6 Case No.: 5Curb Size and Equipment Type: 24”x 24” Gooseneck Relief Air Hood with Flange

Equipment Attachment: Flange Screwed to 22 Gauge Steel Roof Deck Fastener Factor for Each Side of Curb or Protecting Against Hurricanes Flange: 8.1 Case No.: 6Curb Size and Equipment Type: 24”x 24” Gooseneck Relief Air Hood with Flange Equipment Attachment: Flange Screwed to 15/32” OSB Roof Deck Fastener Factor for Each Side of Curb or Flange: 8.2 Case No.: 7

Curb Size and Equipment Type: 24”x 24” Curb with Exhaust Fan Equipment Attachment: Fan Screwed to CurbFastener Factor for Each Side of Curb or Protecting Against Hurricanes Flange: 2.5 Case No.: 8Curb Size and Equipment Type: 36”x 36” Curb with Exhaust FanEquipment Attachment: Fan Screwed to Curb

Fastener Factor for Each Side of Curb or Flange: 3.3 Case No.: 9Curb Size and Equipment Type: 5’-9”x 3’- 8” Curb with 2’- 8” high HVAC UnitEquipment Attachment: HVAC Unit Screwed to CurbFastener Factor for Each Side of Curb or Protecting Against Hurricanes Flange:  

Case No.: 10Curb Size and Equipment Type: 5’-9”x 3’- 8” Curb with 2’- 8” high Relief Air HoodEquipment Attachment: Hood Screwed to CurbFastener Factor for Each Side Protecting Against Hurricanes of Curb or Flange: 35.6* Notes to Table: 1. The loads are based on the 2005 edition of ASCE 7. The resistance includes equipment weight. 

The Base Case of the tabulated numbers of #12 screws (or ¼ pan-head screws for flange-attachment) is a 90-mph basic wind speed, 1.15 importance factor, 30’ building height, Protecting Against Hurricanes Exposure C, using a safety factor of 3.

How Do I Remove Asbestos Siding In North Carolina

A set of index of refraction oils from about n = 1.350 to n = 2.000 in n = 0.005 increments. (Standard for Becke line analysis.) (j) Glass slides with painted or frosted ends 1x3 inches 1mm (thick, precleaned.) Asbestos Abatement How Do I Remove Asbestos Siding In North Carolina Cover Slips 22x22 mm, #1 1/2 (l) Paper clips or dissection needles (m) H  read more..

Is Damage By A Squirrel Covered By Homeowners Ins

The progressive loss of Iowa's woodlands and farmlands to development is increasing the chance for conflicts between humans and wildlife. Social trends, such as increased urbanization, increased populations of certain wildlife species, and finite government resources have combined to provide the   read more..

Broken Pipe In The Wall

Cold Weather Burst Your Pipes?With last week's cold snap bringing below-freezing temperatures, pipes and fixtures around the home were subjected to extreme conditions, and may have been compromised.When water freezes, it expands and can burst water pipes, potentially causing serious property damage&  read more..

Methane Gas Poisoning Symptoms

Standards of Cleanliness Standards of cleanliness for sites used tomanufacture methamphetamine: Methamphetamine: Shall not exceed 0.1 micrograms /100 square centimeters Volatile Organic Chemicals (VOC): Shall not exceed 1 part per million (ppm)total hydrocarbons and VOCs in air under normal inh  read more..

How To Repair A Fire Damaged Wood Floor

Each year the National Fire Protection Association’s (NFPA) Standards Council recognizes individuals for outstanding service to the organization in the development of codes and Fire Damage How To Repair A Fire Damaged Wood Floor standards. Awards will be presented to 35 individuals at the World Safety Conference & Exposition ® taking   read more..

How To Remove Residential Lead Paint

Lead test kits are products sold to consumers for use in detecting the presence of lead.Historically, test kits have been developed to detect lead-based paint as defined by the "Lead Safe Housing Rule," (24 C.F.R. Part 35). Under this rule, administered by the Department of Housing and Urban Develop  read more..

Ceiling Leak Repair Cost

If the water level was less than 2½ feet, the wall material should be removed to a height of 4 feet to facilitate reinstallation of full sheets of drywall. If the water level was greater than 2½ feet, the wall material should be removed to a height of 8 feet or the ceiling junction, whichever is h  read more..

Get Water Stains Out Of Carpet

If you were ordered to evacuate your home, you must check with the mayor's office, town supervisor or local codes enforcement official before returning to your home. Even if you evacuated voluntarily, you should call the town clerk or the building department to ask about the status of buildings in y  read more..

Tenant Junk Removal

Housing codesThe primary purpose of housing codes is to protect the health and safety of the people who live in housesand apartments.A minimum standard of maintenance is set, making the landlord (not the tenant) responsible for keeping Tenant Move Out Cleanup Tenant Junk Removal rental property in decent shape. (See: "The landl  read more..

Mold Remediation From Colorado Flooding

Places that are often or always damp can be hard to maintain completely free of mold. If there's some mold in the shower or elsewhere in the bathroom that seems to reappear, increasing ventilation (running a fan or opening a window) and cleaning more frequently will usually prevent mold from recurri  read more..