Dehumidification >> When Is Dehumidification Required?

The main cooling coil without being re-evaporated by radiant or conducted heat. The main cooling coil must be When Is Dehumidification Required? selected at a coil face velocity at least 150 fpm below the maximum cataloged face velocity to ensure that moisture does not carry over onto a reheat coil (liquid water carryover onto an active reheat coil results in additional energy consumption and humidification).

AHU fans and motors (if the motor is in the air stream) should be located downstream from the recuperative reheat system for optimum effectiveness. If a supplementary reheat coil is When Is Dehumidification Required? used and its leaving-air temperature is above 100 F, then the fan motor must be selected for reliable operation at the actual temperature conditions at the motor. 

It may be necessary to derate the motor and use Class F or H high temperature motor-winding insulation. Special motors are not required for recuperative-reheat systems not equipped with supplementary reheat coils. 

Because of the possibility of moisture condensing on precooling heat-transfer surfaces during part-load operating conditions, provisions for When Is Dehumidification Required? collecting and draining condensate must be made. Heat-exchange surfaces will accumulate particulate even with well maintained filters. Surfaces should be accessible and cleanable without difficulty or high cost.

The fifth recuperative-dehumidification enhancement is superior to the other four in many respects because it achieves almost the same result with a single coil located downstream from the main cooling coil. The single coil reduces first cost, When Is Dehumidification Required? halves the air-side friction of the recuperative elements, and requires no space or modifications upstream from the main cooling coil. 

With the fifth enhancement, which is applicable only to systems using refrigerant coils served by compressors, the amount of reheat is limited. If a significant temperature rise is required, When Is Dehumidification Required? this enhancement may need to be combined with one of the other four. Details on each of the five recuperative-dehumidification enhancements follow. 

Run-around coils for enhanced dehumidification systems are not a new technology. They are well-described in texts from as long ago as 1939.
The psychrometric-chart analysis of run-around coils for precooling and reheating is identical to that for ordinary reheat (see sidebar) with one exception: 

The precooling coil cools the entering air from 84- to 72-F dry bulb (DB); therefore, the air entering the main cooling coil is cooler,When Is Dehumidification Required? which means that the main cooling coil does not have to remove as much heat. The reheat is provided not by an external source of expensive energy, but by the heat picked up by the circulating fluid in the precoil. 

The cycle and savings are illustrated in Figure 2. Figure 3 is a piping diagram showing that run-around coils require a small closed-loop piping system. When freezing is a possibility, the heat-transfer fluid is dilute ethylene glycol; at other times, it is water. The system requires a means of fluid makeup. A diaphragm compression tank normally is installed for fluid expansion. 

If water (not glycol) is used as the circulating fluid and chilled-water or heating-hotwater lines are in the vicinity, When Is Dehumidification Required? it is possible to achieve fill and fluid expansion with a 3 ⁄8-in. connection to the chilled-water or heating-hot-water closed loop. The expansion of the fluid in the small run-around system then would be provided by the fluid-expansion equipment in the larger system.

 With only a single connection between them, there can be no flow between the two systems except for that induced by density forces of water at different temperatures. The system requires a fractional-hp pump, electrical service, When Is Dehumidification Required? and controls. The recommended pump for the circuit is a 120/60/1 hermetically sealed pump that does not require a shaft seal. 

If a pump with a seal is used, the seal should be mechanical rather than packed to minimize or eliminate leakage. The closed-loop piping system is close-coupled and confined to the immediate vicinity of the two coils. 

Once the circulating fluid is charged into the system, there is little possibility of leakage; therefore, When Is Dehumidification Required? the fluid-makeup system can be a hose connection or a funnel fill valve. Coils and piping must include manual air vents at high points to vent air at the time of initial filling. The piping connections to each coil must be arranged for "counterflow.” 

The lines between the two coils (and the coil headers if exposed to ambient air) must be insulated to prevent external heat transfer. The pump should be located in the warm-fluid line. All of the air passing through the air-handling unit must pass through both coils. Any deviations from these guiding principles will cause a loss in performance.

Advantages of runaround coils are:  They can be widely separated and arranged in any position. If desired, When Is Dehumidification Required? a single precooling coil can be used in combination with multiple reheat coils. They carry the certification of the Air-Conditioning and Refrigeration Institute (ARI) and are available from at least 10 manufacturers. 

Because they are mass-produced using machinery, labor contributes little to their cost. They are, for all practical purposes, commodity items and,When Is Dehumidification Required? therefore, relatively inexpensive. Their selection can be made by the manufacturer or by the manufacturer’s coil-selection program using software on a personal computer. 

The precooling and reheat function can be controlled by pump on-off cycling or valve control. The preheat coil can be piped to a third coil in the exhaust-air stream to capture heat for preheating outside air during the winter.

Disadvantages. Disadvantages of run-around-coil systems are: Possible freezing if water is the When Is Dehumidification Required? circulating fluid (this can be overcome by using a dilute ethylene glycol solution selected to provide burst protection at the coldest anticipated entering-air temperature).
 
A 120-v, 60-cycle single-phase electrical circuit is required for the circulating pump. Air trapped in the coils, When Is Dehumidification Required? pump, and piping must be vented upon initial startup to ensure effective fluid flow and heat transfer. Figure 4 shows run-around coils at the entering and leaving sides of a specially configured unit.

Remove The Smell Of Flood Damage From A Home

Don't sign off before the job is finished. Don't sign completion papers or Flood Damage Remove The Smell Of Flood Damage From A Home  ake the final payment until the work is completed to your satisfaction. a reputable contractor will not threaten you or pressure you to sign if the job is not finished properly. 

  read more..

Flood Damage Restoration For Electronics

The second observation is that the first breakdown for the tantalum polymer capacitors occurs at 1.75 times rated voltage. This is roughly twice as high as the lowest voltage seen for the MnO2-based capacitors.While the precise numerical value of this advantage varies somewhat with manufacturer and   read more..

Finger Print Dust Cleanup And Hazard Cleanup

Testimony from other lifeguards pointed out other conditions that injure swimmers or other beach patrons and require the assistance of the lifeguard, thereby resulting in occupational exposure to the lifeguard. Patrons suffer lacerations from rocks, shells, broken glass, fish hooks, Crime Scene Cleanup Finger Print Dust Cleanup And Hazard Cleanup o  read more..

How To Restore Smoke Damaged Archive Photos

If the repository chooses not to use one of the tools cited above, these following questions will help to establish the enduring research or Document restoration How To Restore Smoke Damaged Archive Photos educational value of a collection or a publication in terms of institutional priorities and the overall documentation available on the topic covered:   read more..

Toxic Waste Cleanup

A Crime Scene Cleanup Toxic Waste Cleanup professional supplies a very valuable service to people and their families who endured some kind of a violent crime scene or suicide within their own home. One of these crime scene clean up professionals will usually get things back in order, removing the remnants of the grue  read more..

How To Remove Lead Paint From Old Windows

Renovation, Repair and Painting Program: Property Managers Homes and other buildings built before 1978 are likely to contain lead-based paint. Renovation, repair, or painting work done in those facilities could release hazardous lead dust which could result in lead exposure for your residents.   read more..

How Does Radon Affect Humans

GB - Grab Radon/Pump-Collapsible Bag This method uses a sample bag made of material impervious to radon. At the sample site, a skilled technician using a portable pump fills the bag with air, then transports it to the laboratory for analysis. Usually, the analysis method is to transfer air from the   read more..

Basement Flood Cleanup

When returning to your home after a hurricane or flood, be aware that flood water may contain sewage. Protect yourself and your family by following these steps:Inside the Home Keep children and pets out of the affected area until cleanup has been completed. Wear rubber boots, rubber gloves, and Water Damage Basement Flood Cleanup  read more..

Laws In Wisconsin Regarding Asbestos Siding

Asbestos fibers are a known human carcinogen. Lung cancer, mesothelioma cancer of the chest cavity lining and asbestosisa fibrotic scarring of lung tissue have been proven to result from asbestos exposure. The Clean Air Act (CAA) of 1970 requires Asbestos Abatement Laws In Wisconsin Regarding Asbestos Siding the U.S. Environmental Protection Agency (E  read more..

Flood Damage House

STUDY FACTS:

Power outages were the cause of 18% of water

damage incidents involving a sump pump.

Another 40% of incidents were attributed

to things such as a clogged inlet

screen or a faulty float switch.

LOSS PREVE  read more..