Smoke Damage >> How To Get Rid Of Smoke Odor From Fire

One of the corrosivity tests correlated well with one another or with the leakage current test. As such, it is difficult to draw any specific conclusions as to the quality of particular test. The lack of agreement between generally similar tests (such as ASTM and ISO) serves to illustrate the need to understand complex nature of corrosion phenomena in order to properly assess How To Get Rid Of Smoke Odor From Fire the threat posed by smoke. 

While Chapin et al. [24] claim that circuit bridging is the most important factor in the failure of electronics, How To Get Rid Of Smoke Odor From Fire others have presented cases in which corrosion dominated equipment losses.2.3 Damage Criteria for Electronic Equipment Early reports on non-thermal damage to telecommunications were based on observations of the methods required to recover equipment from fire events. 

These reports categorize the level of damage to equipment based on the acid gas concentration on component surfaces. Both Tewarson and Reagor report that deposited mass of chloride can be a predictor of corrosive damage. However, How To Get Rid Of Smoke Odor From Fire the thresholds specified differ [20,21]. Reagor categorizes four levels of contamination by mass of chloride deposited per unit area.

Clean at less than 2 μg/cm2, easily cleaned and How To Get Rid Of Smoke Odor From Fire recovered below 30 μg/cm2, difficult but possible to recover between 30 μg/cm2 And 90 μg/cm2, and above 90 μg/cm2 it is increasingly likely that the cost of cleaning the component will be greater than simply replacing it. 

Initially, Tewarson specified a minimum concentration of 0.98 μg/cm2 coupled with relative humidity greater than 30 % at 20 °C (68 °F) and How To Get Rid Of Smoke Odor From Fire gas concentrations of 100 ppm HCl or 1000 ppm of NO2, HF, SO2 or acetic acid. In subsequent literature, Tewarson cites Reagor's criteria [28].

Tanaka and Tanaka et al. [18,29] studied failure criteria for digital logic circuits exposed to smoke. In order to evaluate the loss of functionality of the logic circuits, How To Get Rid Of Smoke Odor From Fire the loss of resistance due to smoke was simulated with a variable shunt circuit to determine the point of failure for a range of circuits. Components with a high tolerance to resistance loss are seen to be more tolerant to smoke exposure. 

Critical resistance at failure varied for different chips designs, How To Get Rid Of Smoke Odor From Fire but was highly correlated to the output current of the device. Higher current outputs were seen better able to supply the necessary current to maintain a voltage level despite the loss of resistance due to the shunt. MEASUREMENT OF SMOKE PRODUCTION

During the 1940s and the 1950s, flammability (or "reaction-to-fire") tests were developed on a purely ad hoc basis. Results were typically expressed by arbitrary 0 to 100 scales or How To Get Rid Of Smoke Odor From Fire by such rating terms as "self-extinguishing. " In 1973, the U.S. Federal Trade Commission saw such practices as misleading and sued a number of plastics manufacturers and also the American Society for Testing and Materials (ASTM) [30]. 

A consent agreement was eventually reached whereby a Bunsen burner test, ASTM D 1692, was dropped, and a caveat was inserted into other ASTM tests, How To Get Rid Of Smoke Odor From Fire in an attempt to avoid their future misuse. It is noteworthy that the situation in other countries is similar to the U.S. experience. More than thirty years ago, Emmons obtained the results of flammability tests on a number of materials, when tested according to various national, bench-scale flammability standards [31]. 

He found that the relationship between the test results and real-scale fire behavior according to the different standards was almost completely random. In 1987, –stman and Nussbaum re-examined this issue; the situation appears to have improved only slightly [32]. The reason is that the new knowledge gained in fire physics and How To Get Rid Of Smoke Odor From Fire engineering over the last decades has generally not yet been reflected in many of the required testing standards.

This is due at least partly to the great number of national test methods that exist for fire testing.For example, one such compilation which includes only the ASTM fire test methods tabulates some 167 test standards covering a broad range of measurements. Based on this large number of tests, How To Get Rid Of Smoke Odor From Fire it may seem that fire test methods are highly refined and well tuned to specific areas. 

Though many of the currently published methods were developed up to 40 years ago, for smoke production and for most other fire test results, the focus has shifted to appropriate input data for predictive modeling methods. This chapter provides a review of both types of test methods use to quantify smoke production, How To Get Rid Of Smoke Odor From Fire those that primarily provide a ranking of materials,and those that provide quantitative input for modeling calculations.

Smoke Opacity Testing Typically, How To Get Rid Of Smoke Odor From Fire bench-scale test methods designed to measure the impact of fire smoke provide a measurement of opacity, an indication of visibility through the smoke. The most significant body of work in this area has been accomplished by Jin [34–36], who found that there is an approximate reciprocal relationship between smoke opacity and visibility distance (the distance at which a person can identify an exit sign, for example), according to kV = 2 (1) where k is the smoke extinction coefficient (m-1) and V is the visibility distance (m). 

Thus,measurement of smoke opacity or obscuration is useful in determining the ability to escape or perform needed action in a space during a fire incident. However, How To Get Rid Of Smoke Odor From Fire opacity is the result of the generation of the smoke and not a direct measure of its generation. Opacity results not only from the generation of smoke, but also from agglomeration and surface deposition during transport.

Still, there are a number of widely-used tests that measure smoke opacity. Smoke opacity tests are broadly categorized as either static tests (those in which the smoke generated is allowed to accumulate within the test enclosure) and How To Get Rid Of Smoke Odor From Fire dynamic tests (those in which there is a continuous flow of gases resulting from combustion of the sample).

The Smoke Density Chamber (ASTM E 662) [37], is used widely in testing of materials.Outlined in Figure 5, How To Get Rid Of Smoke Odor From Fire it is a static test that measures smoke generation from small, solid specimens exposed vertically to a radiant flux level of 25 kW/m2in a flaming (piloted ignition)or non-flaming mode. The smoke produced by the burning specimen in the chamber is measured by a light source – photometer combination. 

The attenuation of the light beam by the smoke is a measure of the optical density or "quantity of smoke " that a material will generate under the given conditions of the test. Two measures are typically reported. DS is an instantaneous measure of the optical density at a particular instant in time and How To Get Rid Of Smoke Odor From Fire is expressed as where V is the volume of the chamber (m3), A is the area of the exposed sample (m2), L is the path length of the light beam through the smoke (m), I0 is the intensity of the light beam before the start of the test, and I is the intensity of the light beam during the test.

Tropical Storm Damage

Have your home inspected in accordance with local building codes. Most of the roofs destroyed by tropical storms were destroyed because they were not constructed according to building codes. Seriously consider flood insurance, every Emergency Board up Tropical Storm Damage has a certain amount of flooding. Make a deta  read more..

How To Remove Radon From A Basement

Category I Course Work As stated above, participants in the Residential Mitigation Service Provider component of the RPP must earn a minimum of eight (8) of the required sixteen (16) hours of continuing education every two years through approved Category I course work. Those with dual listings are r  read more..

Learn Water Damage Electronic Restoration

All magnetic parts processed to the Class S requirements of MIL-STD-981 are acceptable as level 1 parts. Magnetics processed to Class B requirements of MIL-STD-981 are acceptable as level 2 parts. All level 1 and 2 custom magnetics shall be processed to the Electronic Restoration Learn Water Damage Electronic Restoration applicable requirements of   read more..

Lead based Paint Is A Common Source Of Lead Poison

Asbestos-containing materials and lead-based paint have the potential to adversely affect human health and the environment. If properly handled, however, the risks are substantially reduced. The abatement of asbestos-containing material and lead-based paint is regulated by various federal, state and  read more..

When Does The Law Require Removal Of Friable Asbes

Compliance program. Where the and/or excursion limit is exceeded, the employer shall establish and implement a written program to reduce employee exposure to or below the and to or below the excursion limit by means of engineering and work practice controls as required by paragraph (f)(1) of this [M  read more..

Emergency Board Up

To contemplate a multi danger mitigation of earthquake and a post-earthquake Smoke Damage Emergency Board Up, both the single structure level and entire region level must be addressed. Lately implementation of structure in fire damage has been accentuated by federal researchers, particularly after the attacks of ‘  read more..

Professional Abandoned House Cleaners

LANDLORD REMEDIES If there is a problem, landlords should immediately notify the tenant and be clear about the violation or breach of the lease agreement, or breach of rules and regulations of the premises. If the tenant does not promptly correct the problem, Tenant Move Out Cleanup Professional Abandoned House Cleaners the landlord has the foll  read more..

Surviving A Tornado

Risk Assessment: Wind/Tornadoes Description The term "straight-line winds" is used to distinguish common, non-rotating winds from tornado-related winds. Straight-line winds are responsible for most thunderstorm wind damage, Wind Damage Surviving A Tornado with wind speeds in excess of 100 miles per hour on occasion.  read more..

Reasons For Sewage Smell From A Basement Drain

Cost effective lift stations are designed to: (1)match pump capacity, type, and configuration with wastewater quantity and quality; (2) provide reliable and uninterruptible operation; (3) allow for easy operation and maintenance of the installed equipment; (4) accommodate future capacity expansion;   read more..

Radon Test Kits

So you have selected a radon test kit and you have tested your home for radon, but now what? This article is for the people who have tested their home for radon and confirmed that yes, they have elevated radon levels, higher than 4 picocuries per liter (pCi/L). Select a highly qualified radon  read more..