Dehumidification >> How To Dehumidify A Flooded Crawl Space

Intuitively, reheating a cooled air stream using hot discharge gas from a refrigerant compressor makes sense. However, it mitigates only the last of the four penalties of ordinary reheat systems mentioned in the sidebar. The refrigeration plant still must be larger by the amount of reheat. Also, the owner must pay the increased operating cost of the amount of How To Dehumidify A Flooded Crawl Space cooling canceled by the reheat. 

Refrigerant hot gas or condenser water reheat is inferior to the other dehumidification enhancements, How To Dehumidify A Flooded Crawl Space particularly when reheat is required on peak design days. This is because it requires a larger cooling-generation system and increased cooling-system operating costs. 

If reheat is required only on mild days and reheat from liquid refrigerant is not a viable solution, How To Dehumidify A Flooded Crawl Space this enhancement can be considered along with the recuperative-dehumidification enhancements discussed previously. Designers of refrigeration systems using hot gas for reheat are cautioned that the design is not as simple as it first appears. 

When the reheat coil is reheating, the cycle is obvious. When the control no longer requires reheat, How To Dehumidify A Flooded Crawl Space the reheat coil will be at a low refrigerant pressure and the coil will fill with condensed liquid refrigerant. When the control again calls for reheat, this liquid refrigerant must be displaced for the reheat coil to function. 

The system must incorporate a larger refrigerant storage vessel and additional refrigerant charge to accommodate the liquid refrigerant that is alternately stored in the reheat coil. Designers have tried numerous ways, How To Dehumidify A Flooded Crawl Space including check valves at the reheat coil outlet, to circumvent this problem. If the check valve holds, the reheat coil will be under very low pressure and invite leaks. 

Most valves have a small leakage rate, How To Dehumidify A Flooded Crawl Space which, in this case, means that the system still must be designed with the extra refrigerant charge and receiver. Some designers suggest bleeding a small amount of hot gas to the reheat coil when reheat is not required. This accomplishes nothing. The coil remains filled with liquid refrigerant. 

Some designers vent the reheat coil to compressor suction pressure when reheat is not required. Although this can be an acceptable solution, How To Dehumidify A Flooded Crawl Space it adds the risk of refrigerant-liquid flood back damaging the compressor when the system changes from reheat to no reheat. A variation of hot-gas reheat involves the use of the warm water leaving a water-cooled refrigerant condenser for reheat. 

This simplifies the refrigerant cycle and is a better alternative if the refrigerant cycle is water-cooled. However, penalties 1, 2, and 3 from the sidebar still apply. CONCLUSION In many cases, How To Dehumidify A Flooded Crawl Space the solution to indoor-air quality and energy efficiency problems can be found in 60- year-old technologies. 

The inventors of these technologies were motivated not so much by the cost of energy, but by the need to reduce compressor size to the limited range of available refrigeration compressors How To Dehumidify A Flooded Crawl Space and to keep electrical motor size to a minimum because of the limited peak power available from the electrical utilities of the 1930s. 

REFERENCES 1) Carrier, Willis H., Realto E. Cherne and Walter A. Grant. "Modern Air Conditioning, Heating, and Ventilating."1940. Pitman Publishing Corp. New York. 2) Ramsey, Melvin A. "Tested Solutions to Design Problems in Air Conditioning and Refrigeration."1966. Industrial Press Inc. New York. 3) Goodman, William. "Air Conditioning Analysis With Psychrometric Charts & Tables."1944. Macmillan Co. New York. 4) Goodman, William (ed.). Trane Air Conditioning Manual. 1939. The Trane Company. La Crosse, Wis. 

The third and final installment of this series will cover passive desiccant enthalpy heat exchangers, heat-powered active desiccant dehumidifiers, and self-contained or How To Dehumidify A Flooded Crawl Space packaged vapor-compression dehumidifiers. Ordinary reheat is not an efficient technology. It is included here to establish a basis of comparison for dehumidification technologies that are more energy-efficient. 

To comprehend the advantages of "enhanced"dehumidification systems, it is vital that owners and HVAC designers understand the four penalties of ordinary reheat systems, which are: 1) The first cost of the cooling generation plant, associated auxiliaries, How To Dehumidify A Flooded Crawl Space and electrical service is increased. 2) The first-cost premium of reheat coils includes increased electrical service and/or heating-distribution piping. 

3) The owner pays the annual operating cost of the additional sensible cooling of air. 4) The owner pays the annual operating cost of reheating air. Although ordinary reheat may be necessary as a final supplement to other forms of reheat, How To Dehumidify A Flooded Crawl Space it should not be used alone or first as a means of humidity control. Review applicable building-energy codes prior to designing or installing a "new-energy"reheat system. 

Reheat systems using "new"energy are restricted under many states building energy codes. Figure 1 is a psychrometric chart for a room with a 12-ton sensible-heat gain, a 7.7-ton latent-heat gain (87 lb or 84 pt of water per hr), a 19.7-ton total-room heat gain, How To Dehumidify A Flooded Crawl Space a 60-percent sensible-heat ratio, and 5000 cfm of outside air, which equates to a 21-ton outside-air load. 

The grand-total load is 40.7 tons, assuming that the HVAC equipment can condition 10,000 cfm of air to a 62-F dry bulb (DB) temperature and a 49-F dew point (DP). Unfortunately, How To Dehumidify A Flooded Crawl Space the constraints associated with the physics of cooling and dehumidifying air result in a cooling coil with a 50-F DB temperature and a 49-F DP. 

Although air at this temperature has enough moisture to absorb 87 lb of water vapor per hr, the 50-F air will over cool the space, causing the thermostat to shut off the cooling and stop further moisture removal. To absorb both the sensible and latent (moisture) gains of the space, How To Dehumidify A Flooded Crawl Space an ordinary-reheat system must utilize 39 KW of reheat. 

This 39 KW causes an 11-ton increase—from 40.7 to 51.7 tons (39 KW [3412 Btu per KWH] / [12,000 Btu per ton-hr] = 11.09 tons)—in the grand total cooling load. At an incremental cost of $550 per ton, How To Dehumidify A Flooded Crawl Space the 11-ton increase adds $6050 in first cost (penalty No. 1). The other three penalties associated with ordinary reheat for this example.

The 39-KW reheat coil (assuming electric) requires electrical circuits and possibly an incremental increase in switch-gear and distribution equipment. At an incremental cost of $50 per KW, this adds $1950 in first cost. n If the reheat coil is energized for dehumidification purposes 1500 hrs per year, an annual operating penalty of $3510 will result, How To Dehumidify A Flooded Crawl Space assuming an average electricity cost of 6 cents per KWH. 

The cooling-generation plant must produce an additional 16,634 ton-hrs of cooling per year, How To Dehumidify A Flooded Crawl Space which results in an annual operating penalty of $998, assuming an average electricity cost of 6 cents per KWH and a plant cooling factor of 1 KW per ton. The load in this example could be managed with either of the following technologies.

Vapor-compression (mechanical) cooling and reheat or (2) drying with a desiccant followed by cooling. At dew-point temperatures above 45 F, cooling with reheat generally is preferred to desiccant dehumidification because of the lower first cost, simplicity, longer life, How To Dehumidify A Flooded Crawl Space and nearly equal or lower operating cost. 

It is important to note that actual annual operating costs could double or triple, particularly if the electric-rate structure involves high demand charges or How To Dehumidify A Flooded Crawl Space ratchet provisions. The preceding analysis did not include the costs of additional cooling-coil heat transfer surface, the reheat coil, or the additional fan energy required because of extra air friction. 

Although these should be included in a detailed analysis, they were omitted here for clarity and How To Dehumidify A Flooded Crawl Space because enhanced-dehumidification options also involve additional heat transfer elements and associated air friction.

Cleanup After Leaking Dishwasher

Health Effects of Exposure to Water-Damaged New Orleans Homes Six Months After Hurricanes Katrina and Rita We identified groupings using a cluster Water Damage Cleanup After Leaking Dishwasher analysis on the natural logarithm of this score. 13 From that we defined an ordinal exposure variable ("exposure to water-damaged homes")   read more..

How To Remove The Smell Of Smoke Damage

Smoke is a complex mixture of carbon dioxide, water vapor, carbon monoxide, particulate matter, hydrocarbons and other organic chemicals, nitrogen oxides, and trace minerals. The individual compounds present in smoke number in the thousands. Smoke composition depends on multiple factors, including t  read more..

How Do I Encapsulate And Dehumidify The Crawl Spac

This Guide for Home Energy Raters presents Guide Details that serve as a visual reference for each of the line items in the Water Management System Builder Checklist. Crawl Space Drying How Do I Encapsulate And Dehumidify The Crawl Spac The details are great tools for Rater education and will help Raters answer contractor and subcontractor questions.&nb  read more..

How To Stop Hoarding Possessions

Pharmacologically, there is little high-quality evidence for benefit of medications. Saxena recently published an open-label study showing positive effects using serotonin reuptake inhibitors (both selective serotonin reuptake inhibitors and serotonin norepinephrine reuptake inhibitors) in OCD and n  read more..

How To Fool A Radon Detector

Provide Information to Consumers and Clients All participants listed for measurement services must provide consumer information, as specified below. This is a continuing requirement of the Program. The EPA may evaluate compliance with this requirement through blind tests for an analytical servi  read more..

Roof Damage Insurance Claim Tips

Roofing systems commonly rely on roof sheathing and bottom chords to provide lateral support for the roof trusses. Oliver and Hanson (1994) and Riba et al. (1994), agree that roofing systems could be considerably improved if simple secondary bracing were installed between Wind Damage Roof Damage Insurance Claim Tips trusses.&nbs  read more..

Basement Sealing

Basement sealing Insulation A properly insulated Basement Drying Basement Sealing can save you money on heating and provide a dry, comfortable living space. In most cases, a basement sealing with insulation installed on its exterior walls should be considered a conditioned space. 

Even in a hou  read more..

Debris Removal

Lead-based house paint was commonly used in homes up until the late 1970s, and was particularly usual before the 1950s. The most customary places to find lead-based house paint are places where high strength is needed, like doors, doorframes, windows, woodwork, and furniture. Lead-based house paint   read more..

How To Raise Houses In Flood Zones

As a result of flooded conditions in homes, large quantities of foodstuffs may be submerged in floodwater or sewerage backflow. While efforts may be made to salvage certain of these foods which havebeen contaminated, Flood Damage How To Raise Houses In Flood Zones  any items cannot be safely salvaged and should be destroyed.&n  read more..

How To Clean Mold On Shower Grout

Always handle bleach with caution. Bleach can irritate the eyes, nose, throat and skin. Never mix bleach with ammonia – toxic chlorine gas may result. Open a window or door to provide fresh air while disinfecting. Protect skin and eyes from contact with bleach. Test solution on a small area befor  read more..