Dehumidification >> What Is A Normal Dehumidifier Setting In Degrees

Recuperative heat exchange is a universal technology applicable to vapor-compression, direct-expansion, and chilled-water air-handling-unit (AHU) coils; heat-powered desiccant dehumidification equipment; dehumidifiers; supermarket, ice-rink, and natatorium air-conditioning and dehumidification systems; and packaged 100-percent-outside-air conditioners. This installment discusses five types of What Is A Normal Dehumidifier Setting In Degrees recuperative sensible-heat exchangers that are used to prevent over cooling while still meeting the dehumidification needs of a conditioned space.
 
 The energy aspects of this technology are explained in great What Is A Normal Dehumidifier Setting In Degrees detail. The reason for this is that many owners and designers are under the incorrect assumption that there are no penalties associated with the use of hot-gas or condenser-water reheat. This is not to say that one should always use some form of recuperative heat exchange in preference to hot-gas or condenser water reheat.
 
It simply is to say that owners and designers should be aware that there is a more energy-efficient way to accomplish reheat while also What Is A Normal Dehumidifier Setting In Degrees reducing the required cooling capacity. Also addressed in this installment are the four penalties associated with ordinary "new-energy” reheat and a technology that is used to avoid one of those penalties: reheat using hot refrigerant gas.
 
RECUPERATIVE DEHUMIDIFICATION
 Recuperative-dehumidification enhancements are good solutions for 100-percent-outside-air cooling units. Five such enhancements are: 1) Coil-loop run-around precooling and What Is A Normal Dehumidifier Setting In Degrees reheating coils (water or glycol). 2) Heat-pipe run-around precooling and reheating coils. 3) Air-to-air flat-plate heat exchangers for precooling and reheating. 4) Rotary-wheel heat exchangers for precooling and reheating. 5) Refrigerant liquid subcooling/airreheating coil.
 
Each of the first four enhancements involves one heat-transfer device located upstream from the main cooling coil and one heat-transfer device located downstream from the main cooling coil. The What Is A Normal Dehumidifier Setting In Degrees upstream device precools air as it enters the main cooling coil, while the downstream device reheats the air by the same enthalpy change as it leaves the main cooling coil. Other than a small increase in fan energy to overcome the added air friction of the precooling and reheating sections and a fractional-hp pump for the coil-loop enhancement, no external energy is used.
 
 (If the heattransfer devices are active for only a small portion of the annual operating hours, consider bypass dampers to reduce the annual energy impact.) The first four enhancements can be applied to any type of primary cooling coil: chilled water, chilled What Is A Normal Dehumidifier Setting In Degrees glycol, or refrigerant. If the primary coil is of the refrigerant type, then the performance of the refrigeration system must be verified at mild- and cool-weather entering-air conditions to ensure that the refrigeration system will operate without compressor cycling or liquid slugging and with proper oil return.
 
 Suction temperatures above 30 F are necessary to prevent frost or ice accumulation on the main cooling coil. The performance of 100-percentoutside-air recuperative-dehumidification What Is A Normal Dehumidifier Setting In Degrees enhancements varies from a maximum temperature change at peak cooling conditions to no temperature change at an outside temperature of approximately 50 F. This performance usually is acceptable because the latent load of the outside air declines with outside temperature.
 
Applications must be analyzed to determine if additional reheat (from hot refrigerant gas, electric heating coils, thermal heating coils, or in-space heat sources) is required to maintain acceptable space conditions. Supplementary reheat coils, if required, must be located What Is A Normal Dehumidifier Setting In Degrees downstream from the recuperative-dehumidification reheat coil. Heating, recuperative-reheat, and conventional reheat coils must be separated from the main cooling coil to allow condensed moisture to drain from the main cooling coil without being re-evaporated by radiant or conducted heat.
 
 The main cooling coil must be selected at a coil face velocity at least 150 fpm below the maximum cataloged face velocity to ensure What Is A Normal Dehumidifier Setting In Degrees that moisture does not carry over onto a reheat coil (liquid water carryover onto an active reheat coil results in additional energy consumption and humidification). AHU fans and motors (if the motor is in the air stream) should be located downstream from the recuperative reheat system for optimum effectiveness.
 
If a supplementary reheat coil is used and its leaving-air temperature is above 100 F, then the fan motor must be selected for reliable operation at the actual temperature conditions at the motor. It may be necessary to de-rate the motor and use Class F or H high What Is A Normal Dehumidifier Setting In Degrees temperature motor-winding insulation. Special motors are not required for recuperative-reheat systems not equipped with supplementary reheat coils. Because of the possibility of moisture condensing on precooling heat-transfer surfaces during part-load operating conditions, provisions for collecting and draining condensate must be made.
 
 Heat-exchange surfaces will accumulate particulate even with well maintained filters. Surfaces should be accessible and cleanable without difficulty or high cost. The fifth recuperative-dehumidification enhancement is superior to the other four in many respects because it achieves almost the same result with a single coil located What Is A Normal Dehumidifier Setting In Degrees downstream from the main cooling coil. The single coil reduces first cost, halves the air-side friction of the recuperative elements, and requires no space or modifications upstream from the main cooling coil.
 
With the fifth enhancement, which is applicable only to systems using refrigerant coils served by compressors, the amount of What Is A Normal Dehumidifier Setting In Degrees reheat is limited. If a significant temperature rise is required, this enhancement may need to be combined with one of the other four. Details on each of the five recuperative-dehumidification enhancements follow.
 
 COIL-LOOP RUN-AROUND PRECOOLING, REHEATING
Run-around coils for enhanced dehumidification systems are not a new technology. They are well-described in texts from as long ago as 1939.1, 2, 3, 4 The psychrometric-chart analysis of run-around coils for precooling and reheating is identical to that for What Is A Normal Dehumidifier Setting In Degrees ordinary reheat (see sidebar) with one exception: The precooling coil cools the entering air from 84- to 72-F dry bulb (DB); therefore, the air entering the main cooling coil is cooler, which means that the main cooling coil does not have to remove as much heat.
 
The reheat is provided not by an external source of expensive energy, but by the heat picked up by the circulating fluid in the precoil. The cycle and savings are illustrated in Figure 2. Figure 3 is a What Is A Normal Dehumidifier Setting In Degrees piping diagram showing that run-around coils require a small closed-loop piping system. When freezing is a possibility, the heat-transfer fluid is dilute ethylene glycol; at other times, it is water.

Natural Disaster Damage

You could also collect some rainwater and Flood Damage Natural Disaster Damage from streams, rivers, ponds, lakes, and natural springs. But you must be sure you boil any water you plan to drink or use for cooking. Do not drink any floodwater, which is very likely to be contaminated; water from water beds, which has pesticide  read more..

How Do I Remove Asbestos Siding In North Carolina

A set of index of refraction oils from about n = 1.350 to n = 2.000 in n = 0.005 increments. (Standard for Becke line analysis.) (j) Glass slides with painted or frosted ends 1x3 inches 1mm (thick, precleaned.) Asbestos Abatement How Do I Remove Asbestos Siding In North Carolina Cover Slips 22x22 mm, #1 1/2 (l) Paper clips or dissection needles (m) H  read more..

How To Remove Fire Smoke Smell From Apartment

Proper selection of PPE for individual responders must be based upon a careful assessment of two factors: (1) the hazards anticipated to be present, or are present at the scene and (2) the probable impact of those hazards, based upon the mission role of the individual. The emergency responder must b  read more..

Use A Crawlspace Dehumidifier In Your Crawlspace

Select an appropriate winter vacation temperature setting: 37. When leaving your home unoccupied during periods of both mild and severe winter temperatures, finding the right temperature setting can be a challenge. Crawl Space Drying Use A Crawlspace Dehumidifier In Your Crawlspace. It requires balancing the need to minimize the amount of heat added t  read more..

Solutions For A Building In A Flood Zone

During a ceremony today at Anderson University, the U.S. Environmental Protection Agency (EPA) announced a $60,000 award to Upstate Forever to help restore the Rocky River and its associated wetlands in Anderson, S.C., support community revitalization and Flood Damage Solutions For A Building In A Flood Zone protect public health.

  read more..

Sick Building Syndrome

Psychological factors Excessive work stress or dissatisfaction, poor interpersonal relationships and poor communication are often seen to be associated with SBS. Poor and inappropriate lighting with absence of sunlight, bad acoustics, poor ergonomics Radon Mitigation Sick Building Syndrome and humidity may also contribute t  read more..

Coyote Control Skunk Removal

The Eastern coyote is firmly recognized in the U.S. Most Animal Damage Coyote Control Skunk Removal difficulties involve sheep or free ranging chickens and ducks. Most difficulties can be evaded with proper husbandry methods. It is much easier to prevent plunder from happening than it is to stop it once it starts. Below are some step  read more..

Wet Carpet From Basement Flood

What is mold? Mold is a general term used to describe a type of fungus. There are many different types of molds and they are common throughout nature. Molds may vary in color and appearance. Some molds may be seen on foods, damp surfaces, cloth and other porous materials, Water Damage Wet Carpet From Basement Flood and may be r  read more..

Wind Structural Design

Wind forces are also hazards to foundations. Wind pressure against the walls of an elevated house produce enormous strain on the superstructure-to-foundation Wind Damage Wind Structural Design connection. 

Further, poorly embedded pile-and-pier foundations are subject to racking (horizo  read more..

Water Carpet In A Basement

Restoration Practices WRP projects are aimed at restoring or enhancing wetland functions, but also reflect a programmatic emphasis on wildlife benefits and the landowners' interests. Nearly 60% of project files indicated an explicit or implicit goal of managing the restored wetlands as waterfow  read more..